FCS-320-TM Aspirating Smoke Detector
2.6

Pipe system components

2.6.1

Overview

A
3
Figure 2.15 Pipe system components
During planning/design, a distinction is drawn between area monitoring and equipment
monitoring. For both applications, PVC pipes and halogen-free pipes can be used. The pipes
used for equipment monitoring should be halogen-free.
Figure 2.15 shows essential accessory components that can be selected for the application
concerned.
The pipe system must be constructed using pipes with an external diameter of 25 mm and the
associated fittings.
blowing-out system
In areas that are susceptible to dust particles or icing, it may be necessary to blow out the
aspiration pipe system and its air sampling openings. Figure 2.16 shows a manual blowing-out
system with a three-way tap.
Figure 2.16 Components of manual blowing-out systems
Bosch Sicherheitssysteme GmbH
5
A
4
A
2
1
A
B
Operation Guide
6
7
9
8
10
B
11
12
13
14
1
2
A
Technical Specifications | en
A
Pipe system connection
B
Smoke aspiration pipe
1
Connection for test adapter
2
T-fitting
3
Air filter
4
Water separator
5
Detonation safety barrier
(not permitted for EN 54-20)
6
90° pipe bend
7
Aspiration hose for ceiling
lead-through
8
Ceiling Lead-through
Adapter
9
fitting
10
Double threaded joint
11
90° pipe elbow
12
45° pipe elbow
13
Aspiration reduction
14
End cap
A
Blast air supply connection
B
Pipe system connection
1
Three-way tap
2
25 mm aspiration pipe
Aspiration reducing clips
F.01U.130.928 | 1.0 | 2009.11