Guide to updating a redundant Route Control server in runtime

6.12.1

Updating a redundant Route Control server in runtime

For servers and single-station systems which are used for OS and Route Control, please
observe the following information.
Requirement
● The Route Control project on the engineering station has been updated.
● Note the phases in section "Guidelines for updating a redundant OS in runtime (Page 208)".
Note
Backing up the log files
Back up the log files before replacing or reinstalling a computer, at the latest. You can find
the configured storage path via the Route Control Engineering (list for route log in the path:
Project Settings > Runtime Parameters > Routes Log > Values for Server and Standby).
Procedure
Execute the following steps on the servers, note the sequence and the states on each PC
station.
Default Master
1.
V7.x SPx
– Runtime
(2)
2.
V7.x SPx
– Runtime
(2)
3.
V7.x SPx
– Runtime
(2)
4.
V7.x SPx
– Runtime
(2)
Do not update the current server (default master)!
5.
The default master continues to operate as standby
server
6.
Exit RC server
7.
Execute an update installation on the default master. New version – Runtime
The next step involves changing the master role.
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA
6.12 Guide to updating a redundant Route Control server in runtime
(1)
Failure, Switchover and Return of Fault-tolerant Components
Default Standby
(1)
V7.x SPx
– Runtime
(2)
Exit Runtime
Execute an update installation on the "Default Standby Serv‐
er" and the Engineering Station.
Update the database to the new version and download it
(you may have to update and download the WinCC project)
Start the RC server (and also WinCC Runtime, if needed)
and perform the update (the default standby server must be
selected on a client with a new version in the RC Center
using the menu command Program > Server Selection)
Activate the default standby
This RC server becomes the master (new version – Runtime)
● RC clients with V7.x SPx
connection to an RC server of another version is not
possible.
● RC clients with the new version connect to the RC server
● All running routes will be processed with the new RC
server.