How To Set The Redundancy Connection For Batch Servers; How To Download The Target Systems For Simatic Batch - Siemens SIMATIC PCS 7 Function Manual

Fault-tolerant process control systems (v8.1)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Additional information
● Manual
4.6.6

How to set the redundancy connection for BATCH servers

Introduction
You will now select the connection path for the redundancy connection between 2 BATCH
servers.
You can make the following settings directly on each of the mutually redundant BATCH servers.
Note
Shared server for OS and SIMATIC BATCH
The configuration for redundancy connection has to be performed only once.
Requirements
● BATCH server and BATCH partner server are connected to an additional network adapter
via a redundancy cable.
● BATCH server and BATCH partner server are installed as redundant BATCH servers.
Procedure
1. Open the Windows Explorer on the BATCH server.
2. Select the folder My Computer > Simatic Shell in the tree view.
3. In the shortcut menu, select the menu command Set Redundancy ....
The "Redundancy Settings" dialog box opens.
4. In the drop-down list under the "Network Adapter" group, select the network adapter through
which the redundancy communication to the partner server should be established.
5. Perform steps 1 to 4 for each partner server.
4.6.7

How to download the target systems for SIMATIC BATCH

Introduction
You can download a PCS 7 project that you created in SIMATIC Manager along with the
components of the project (AS, OS, BATCH server/client) to the various target systems in a
single step with the menu command PLC > Compile/Download Programs.
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA
Process Control System PCS 7; SIMATIC BATCH
Advantages of fault-tolerant components
4.6 SIMATIC BATCH Stations
167