Siemens SIMATIC PCS 7 Function Manual page 134

Fault-tolerant process control systems (v8.1)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Advantages of fault-tolerant components
4.4 Distributed I/O
Procedure
1. Configure redundant modules for HART field devices in HW Config as described in section
"How to configure redundant I/O modules (Page 129)".
In the example, the module on slot 6 is configured in each case:
– ET 200M station with PROFIBUS address 4: Module 6
– ET 200M station with PROFIBUS address 6: Module 6
2. Place the "HART field device" in the detail view of the redundant module.
In the example, module 6 on ET 200M station with PROFIBUS address 4.
134
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA