Guide To Updating A Redundant Batch Server In Runtime - Siemens SIMATIC PCS 7 Function Manual

Fault-tolerant process control systems (v8.0)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

6.11

Guide to updating a redundant BATCH server in runtime

6.11.1
Software update (migration)
Information is available in the SIMATIC BATCH product documentation:
● Operating Manual
6.12
Guide to updating a redundant Route Control server in runtime
6.12.1
Updating a redundant Route Control server in runtime
For servers and single-station systems which are used for OS and Route Control, please
observe the following information.
Requirement
● The Route Control project on the engineering station has been updated.
● Note the phases in section "Guidelines for updating a redundant OS in runtime (Page 191)".
Procedure
Execute the following steps on the servers, note the sequence and the states on each PC
station.
Default Master
1.
V7.x SPx
– Runtime
(2)
2.
V7.x SPx
– Runtime
(2)
3.
V7.x SPx
– Runtime
(2)
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02
6.12 Guide to updating a redundant Route Control server in runtime
SIMATIC Process Control System PCS 7; SIMATIC BATCH; section
"Software update (Migration)."
NOTICE
Backing up the log files
Back up the log files before replacing or reinstalling a computer, at the latest. You can
find the configured storage path via the Route Control Engineering (list for route log in the
path: Project Settings > Runtime Parameters > Routes Log > Values for Server and
Standby).
(1)
Failure, Switchover and Return of Fault-tolerant Components
Default Standby
(1)
V7.x SPx
– Runtime
(2)
Exit Runtime
Execute an update installation on the "Default Standby
Server" and the Engineering Station.
Update the database to the new version and download it
(you may have to update and download the WinCC project)
207