Route Control Clients; Failover Reaction Of Route Control Clients - Siemens SIMATIC PCS 7 Function Manual

Fault-tolerant process control systems (v8.1)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

6.9

Route Control clients

6.9.1

Failover reaction of Route Control clients

Functionality
If the master Route Control server fails, the Route Control clients are automatically switched
over to the redundant Route Control server.
Reactions during failover
During a failover, a message window is displayed on the screen of the Route Control client
indicating the failover. The Route Control client cannot be operated during this time. The
message window closes and the Route Control client can be operated again only when the
failover from the failed Route Control server to the redundant Route Control server is complete.
Note
The route can be controlled from a Route Control faceplate during the switchover of a Route
Control server.
Additional information
● Manual
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA
Failure, Switchover and Return of Fault-tolerant Components
Process Control System PCS 7; SIMATIC Route Control
6.9 Route Control clients