Advantages of fault-tolerant components
4.2 SIMATIC H Station
4.2
SIMATIC H Station
4.2.1
Overview of configuration tasks
Overview of configuration tasks
You configure the redundancy functionality of the SIMATIC fault-tolerant station (H station) by
performing the following steps:
Step
1
2
3
4
4.2.2
How to add a SIMATIC H station to your project
Introduction
The SIMATIC H station is contained in the hardware catalog of HW Config as a stand-alone
station type. This station type is required if you want to configure two central devices each with
a H CPU, thereby configuring the entire process control system with redundancy.
The direct connection of a singular CPU to the redundant, fault-tolerant plant bus is possible
with a CPU 410H.
Procedure
1. Open your PCS 7 project in the component view of SIMATIC Manager.
2. Select the menu command View > Component View.
3. Select the project.
4. Select the following menu command: Insert > Station > SIMATIC H Station.
5. Click the inserted SIMATIC H station.
100
What?
Inserting a SIMATIC H station in a project (Page 100)
Inserting synchronization modules in the H_CPU (Page 102)
Configuring redundant communications processors (Page 103)
Setting the CPU for the error response of input/output modules (Page 105)
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA