4.3.5

How to configure a fault-tolerant fieldbus on the basis of PROFINET

Introduction
The following section describes how to create and connect a fault-tolerant fieldbus on the basis
of PROFINET.
● Configure the components in HW Config.
● In the Topology Editor, configure the connections between the components in accordance
with the cable sequence in the system.
Requirements
● The PCS 7 project with a SIMATIC H station is open in SIMATIC Manager.
● HW Config is open.
● The redundant backplane is inserted in HW Config.
● In HW Config, each rack has been fitted with an 4xx-xH PN/DP H CPU and the required
synchronization modules.
● The PROFINET IO systems are added to the H-CPU. This can be done using Insert on the
H‑CPU.
Configuring in HW Config
1. In the hardware catalog, open the PROFINET IO > I/O > ET 200M folder.
2. Select the version of the interface module (IM 153-4 ...) you are using and move it onto the
PROFINET IO system using drag-and-drop.
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA