Fault-tolerant Solutions in PCS 7
3.3 Solutions for communication
The following figure shows this configuration.
Note
Redundant linking of network segments
The redundant linking of two network segments is only possible when the linking switches are
capable of acting as standby manager.
Example:
● Linking with SCALANCE X414-3E
● For Gigabit Ethernet: Linking with SCALANCE X408-2
Redundant, fault-tolerant terminal bus with redundant linking of network segments (rings)
One pair of redundancy-capable network adapters is used for each PC station in each server
to be connected to the terminal bus (for example, OS server, BATCH server, domain
controller); see section "Connecting PC stations to the terminal bus (Page 51)". Team-capable
network adapters are required for this configuration. They work in " INTEL Team mode" with
only one logical network address. Each network adapter is connected to one of the redundant
terminal bus rings (bus1/bus2). The link between the redundant network segments (rings) is
implemented using two switches in each network.
58
Fault-tolerant Process Control Systems (V8.1)
Function Manual, 11/2014, A5E34878832-AA