3.2.3 Settings When Using Expansion Unit

Make the settings according to the used configuration.
 Selection of Power supply unit and Expansion unit
Setting item
Common to
Base and
Power
Expansion
supply unit
1-3
Expansion
Base
unit
Expansion
Expansion
1-3
unit
Common to
Expansion
Base and
unit startup
Expansion
wait time
1-3
Description
Select 24 V DC or a power supply unit according to the used configuration.
AFPEXPM (Master, short distance): Select when the total length of expansion
cables is 9 m or less.
AFPEXPM (Master, long distance): Select when the total length of expansion
cables is 10 m or more.
Select AFP7EXPS (Slave).
Set the wait time until the power to the expansion unit turns ON after the power to
the CPU unit turned ON. A self-diagnostic error occurs when the power to the
expansion unit does not turn on even after the elapse of the startup wait time.
Communication via the USB port , COM port and LAN port of the CPU unit
cannot be performed during the startup wait time.
Setting range: 5 to 1800 secs, Default: 5 secs
3.2 Optional Allocation Using FPWIN GR7
3-9