3.2.3 Settings When Using Expansion Unit
Make the settings according to the used configuration.
Selection of Power supply unit and Expansion unit
Setting item
Common to
Base and
Power
Expansion
supply unit
1-3
Expansion
Base
unit
Expansion
Expansion
1-3
unit
Common to
Expansion
Base and
unit startup
Expansion
wait time
1-3
Description
Select 24 V DC or a power supply unit according to the used configuration.
AFPEXPM (Master, short distance): Select when the total length of expansion
cables is 9 m or less.
AFPEXPM (Master, long distance): Select when the total length of expansion
cables is 10 m or more.
Select AFP7EXPS (Slave).
Set the wait time until the power to the expansion unit turns ON after the power to
the CPU unit turned ON. A self-diagnostic error occurs when the power to the
expansion unit does not turn on even after the elapse of the startup wait time.
Communication via the USB port , COM port and LAN port of the CPU unit
cannot be performed during the startup wait time.
Setting range: 5 to 1800 secs, Default: 5 secs
3.2 Optional Allocation Using FPWIN GR7
3-9