Panasonic FP7 Series User Manual page 117

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

Error codes 20 to 27
Code
Name
20
Syntax error
21
Duplicated use
22
Not paired
24
Program area error
High-level instruction
25
execution
combination error
Compile memory full
27
error
(Note) For errors where "Auto clear" is indicated in the 'Operation' column, error clearance is executed when power
supply is cut off, or when the unit is set to the RUN mode again after the status has been corrected.
Operation
Stop
A program with a syntax error has been written. Switch to the
Auto clear
PROG. mode and correct the error.
The same relay is used multiple times in OT instruction, etc.
Switch to the PROG. mode and correct the error. Or, set the
duplicated output to "enable" in the CPU configuration.
Stop
Auto clear
Applicable devices and instructions are as follows.
• Operation device (X, Y, R, L), timer/counter instruction, SSTP
instruction
For instructions which must be used in a pair, one instruction is
either missing or in an incorrect position. Switch to the PROG.
mode and enter the two instructions which must be used in a
pair in the correct positions.
Applicable instructions and cases are as follows.
Stop
• MC and MCE are not paired.
Auto clear
• LBLs corresponding to LOOP and JP are not located in the
same area (normal program area / same sub-routine area /
same interrupt program area).
• There are no sub-routines corresponding to CALL and
FCALL.
• There is no STPE corresponding to SSTP.
An instruction that can only executed in a specified area is
written in another location. Switch to the PROG. mode and
correct the error.
Applicable instructions and cases are as follows.
• LBL, LOOP, JP, MC and MCE are in the stepladder area.
• MC is nested in more than 16 layers.
• CNDE is outside the normal program area.
Stop
• EDPB is outside the blank area.
Auto clear
• ED is inside the sub-routine area or the interrupt area.
• SBL is outside the blank area or the sub-routine area.
• An interrupt program is outside the blank area or the interrupt
program area.
• RET is outside the sub-routine area.
• IRET is outside the interrupt program area.
• STPE is outside the stepladder area.
In the program, high-level instructions, which execute in every
scan and at the leading edge of the trigger, are programmed to
Stop
be triggered by one contact. Correct the program so that the
Auto clear
high-level instructions executed in every scan and only at the
leading edge are triggered separately.
The program is too large to compile in the program memory.
Stop
Switch to the PROG. mode and reduce the total number of
Auto clear
steps for the program.
8.1 CPU Unit Specifications
Error contents and steps to take
8-21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp7cps21Afp7cps31Afp7cps31eAfp7cps41e

Table of Contents