Connection examples for redundant I/Os
E.22 SM 332; AO 4 x 0/4...20 mA [EEx ib], 6ES7 332–5RD00–0AB0
E.22
SM 332; AO 4 x 0/4...20 mA [EEx ib], 6ES7 332–5RD00–0AB0
The diagram below shows the connection of an actuator to two SM 332; AO 4 x 0/4...20 mA
[EEx ib]. The actuator is connected to channel 0.
Suitable diodes are, for example, types from the series 1N4003 ... 1N4007 or any other
diode with U
Figure E-22
482
>=200 V and I_
>= 1 A
_r
F
Example of an interconnection with SM 332; AO 4 x 0/4...20 mA [EEx ib]