Pcs 7, Step 2: Editing And Downloading The User Program - Siemens SIMATIC S7-400H System Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

17.4.2

PCS 7, step 2: Editing and downloading the user program

Starting situation
The fault-tolerant system is operating in redundant system mode.
The following program modifications are not possible in redundant system mode and result
in the system mode Stop (both CPUs in STOP mode):
 Structural modifications to an FB interface or the FB instance data.
 Structural modifications to global DBs.
 Compression of the CFC user program.
Before the entire program is recompiled and reloaded due to such modifications the
parameter values must be read back into the CFC, otherwise the modifications to the block
parameters could be lost. You will find more detailed information on this topic in the
S7, Continuous Function Chart
Procedure
1. Edit only the program elements related to the hardware removal. You can delete the
2. In SIMATIC Manager, select the charts folder and choose the "Options > Charts >
3. Compile only the modifications in the charts and download them to the target system.
Result
The fault-tolerant system continues to operate in redundant system mode. The modified user
program will no longer attempt to access the hardware being removed.
S7-400H
System Manual, 03/2012, A5E00267695-11
CAUTION
following components:
– CFCs and SFCs
– Blocks in existing charts
– Channel drivers, interconnections and parameter settings
Generate Module Drivers" menu command.
This removes the driver blocks that are no longer required.
NOTICE
Until an FC is called the first time, the value of its output is undefined. This must be
taken into account in the interconnection of the FC outputs.
manual.
System modifications during operation
17.4 Removing components in PCS 7
CFC for
297

Advertisement

Table of Contents
loading

Table of Contents