Time synchronization via the PROFINET interface
At the PROFINET interface, time synchronization is possible using the NTP method. The
PROFINET CPU is client.
You may configure up to four NTP servers. You can set the update interval between 10
seconds and 1 day. If times exceed an interval of 90 minutes, the PROFINET CPU requests
an NTP at cyclic intervals of 90 minutes.
If synchronizing the PROFINET CPU based on the NTP method, you should configure the
PROFINET CPU as the time master for the synchronization method in the S7-400. Select a
synchronization interval of 10 seconds.
Use FB "LT_BT" or FB "BT_LT" from the STEP 7 standard library to make allowances for a
time zone or daylight saving/standard time.
Time synchronization is also possible via Ethernet MMS as master or slave. The
combination NTP with SIMATIC method is allowed in this case.