Sm 322; Do 8 X Dc 24 V/2 A, 6Es7 322-1Bf01-0Aa0 - Siemens SIMATIC S7-400H System Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Connection examples for redundant I/Os
E.14 SM 322; DO 8 x DC 24 V/2 A, 6ES7 322–1BF01–0AA0
E.14
SM 322; DO 8 x DC 24 V/2 A, 6ES7 322–1BF01–0AA0
The diagram below shows the connection of an actuator to two redundant SM 322; DO 8 x
DC 24 V. The actuator is connected to channel 0.
Types with U
Figure E-14
474
>=200 V and I_
>= 2 A are suitable as diodes
_r
F
Example of an interconnection with SM 322; DO 8 x DC 24 V/2 A
System Manual, 03/2012, A5E00267695-11
S7-400H