Technical data
Technical data
Maximum distance between the
CPUs
Power supply
Current consumption
Power loss
Wavelength of the optical
transceiver
Maximal permitted attenuation of the
fiber-optic cable
Maximum permitted difference in
cable lengths
Dimensions W x H x D (mm)
Weight
See also
Installation of fiber-optic cables (Page 346)
S7-400H
System Manual, 03/2012, A5E00267695-11
18.1 Synchronization modules for S7–400H
6ES7 960–1AA06–0XA0
10 m
3.3 V, supplied by the CPU
220 mA
0.77 W
850 nm
7.5 dB
9 m
13 x 14 x 58
0.014 kg
Synchronization modules
6ES7 960–1AB06–0XA0
10 km
3.3 V, supplied by the CPU
240 mA
0.83 W
1310 nm
9.5 dB
50 m
13 x 14 x 58
0.014 kg