System modifications during operation
17.8 Changing the CPU memory configuration
Procedure
Proceed as follows in the specified sequence:
Step
What to do?
1
Switch the reserve CPU to STOP using the
programming device.
2
Replace the memory card in the CPU with a card
which has the required (higher) capacity.
3
Reset the reserve CPU using the programming
device.
4
Start the reserve CPU with the menu command "PLC
> Mode > Switch to CPU ... with expanded memory
configuration".
5
Turn off power to the second CPU.
6
Modify the memory configuration of the second CPU
as you did in steps 2 to 3 for the first CPU.
7
Start the second CPU with the menu command "PLC
> Mode > Switch to CPU ... with expanded memory
configuration".
330
How does the system react?
The system is now operating in single mode.
Reserve CPU requests memory reset.
The reserve CPU links up, is updated and
becomes the master.
Previous master CPU changes to STOP.
System operates in single mode.
The subsystem is disabled.
The second CPU is linked up and updated.
The system is now operating again in redundant
system mode.