Starting situation for replacement of the load memory
Failure
The S7-400H is in redundant system mode and a
load memory access error occurs.
Procedure
Follow the steps below to replace the load memory:
Step
1
2
3
S7-400H
System Manual, 03/2012, A5E00267695-11
16.2 Failure and replacement of components during operation
What has to be done?
Perform a CPU memory reset on the
replaced CPU.
Start the replaced CPU (for example, STOP-
RUN or Start using the PG).
What has to be done?
Replace the memory card on the stopped
CPU.
Perform a memory reset on the CPU with the
replaced memory card.
Start the CPU.
Failure and replacement of components during operation
How does the system react?
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN and operates
as the reserve CPU.
How does the system react?
The relevant CPU changes to STOP and
requests a memory reset.
The partner CPU switches to single mode.
How does the system react?
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN and operates
as the reserve CPU.