S7-400 cycle and response times
19.5 Response time
Table 19- 11 Direct access of the CPUs to I/O modules in the expansion unit with local link
Access mode
412-5H
stand-
alone
mode
Read byte
6.0 µs
Read word
11.0 µs
Read double
20.0 µs
word
Write byte
5.3 µs
Write word
10.6 µs
Write double
19.8 µs
word
Table 19- 12 Direct access of the CPUs to I/O modules in the expansion unit with remote link, setting 100 m
Access mode
412-5H
stand-
alone
mode
Read byte
11.5 µs
Read word
23.0 µs
Read double
46.0 µs
word
Write byte
11.0 µs
Write word
22.0 µs
Write double
44.5 µs
word
Note
You can also achieve fast response times by using hardware interrupts; see section Interrupt
response time (Page 379).
374
412-5H
414–5H
redundant
stand-
alone
mode
36.0 µs
5.6 µs
41.3 µs
10.5 µs
49.0 µs
19.9 µs
35.3 µs
5.3 µs
41.3 µs
10.2 µs
49.0 µs
19.8 µs
412-5H
414–5H
redundant
stand-
alone
mode
41.3 µs
11.5 µs
49.0 µs
23.0 µs
72.1 µs
46.0 µs
41.3 µs
11.0 µs
49.0 µs
22.0 µs
72.1 µs
44.5 µs
414–5H
416-5H
redundant
stand-
alone
mode
24.5 µs
5.6 µs
32.1 µs
10.5 µs
40.0 µs
19.9 µs
5.3 µs
24.5 µs
28.6 µs
10.2 µs
39.8 µs
19.8 µs
414–5H
416-5H
redundant
stand-
alone
mode
27.5 µs
11.4 µs
39.8 µs
22.8 µs
62.9 µs
45.9 µs
10.8 µs
27.0 µs
39.8 µs
21.9 µs
62.9 µs
44.0 µs
416-5H
417–5H
redundant
stand-
alone
mode
16.1 µs
5.6 µs
23.8 µs
10.5 µs
31.7 µs
19.9 µs
16.1 µs
5.3 µs
21.5 µs
10.2 µs
31.5 µs
19.8 µs
416-5H
417–5H
redundant
Einzel-
betrieb
20.3 µs
11.3 µs
31.5 µs
22.8 µs
54.5 µs
45.9 µs
20.2 µs
10.8 µs
31.5 µs
21.9 µs
54.5 µs
44.0 µs
System Manual, 03/2012, A5E00267695-11
417–5H
redundant
13.4 µs
18.6 µs
28.7 µs
13.4 µs
18.3 µs
28.0 µs
417–5H
redundant
17.0 µs
28.6 µs
51.7 µs
16.8 µs
27.8 µs
50.0 ms