System modifications during operation

17.9 Re-parameterization of a module

17.9
Re-parameterization of a module
17.9.1
Re-parameterization of a module
Refer to the information text in the "Hardware Catalog" window to determine which modules
(signal modules and function modules) can be reconfigured during ongoing operation. The
specific reactions of individual modules are described in the respective technical
documentation.
NOTICE
If you edit any protected parameters, the system will reject any attempt to changeover to
the CPU containing those modified parameters. The event W#16#5966 is written to the
diagnostic buffer. and you will then have to restore the wrongly changed parameters in the
parameter configuration to their last valid values.
The selected new values must match the current and the planned user program.
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
To edit the parameters of modules in a fault-tolerant system, perform the steps outlined
below. Details of each step are described in a subsection.
Step
What to do?
1
Editing parameters offline
2
Stopping the reserve CPU
3
Downloading modified CPU parameters to the reserve
CPU
4
Switching to CPU with modified configuration
5
Transition to redundant system mode
334
See section
Step 1: Editing parameters offline (Page 335)
Step 2: Stopping the reserve CPU (Page 336)
Step 3: Downloading a new hardware
configuration to the reserve CPU (Page 336)
Step 4: Switching to CPU with modified
configuration (Page 337)
Step 5: Transition to redundant system mode