Siemens SIMATIC S7-400H System Manual page 185

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

The valid values that can be processed by the user program are always located at the lower
address of both redundant modules. This means that only the lower address can be used for
the application; the values of the higher address are not relevant for the application.
Note
Use of FB 450 "RED_IN" and 451 "RED_OUT" when using process image partitions
For each priority class used (OB 1, OB 30 ... OB 38), you must use a separate process
image partition.
S7-400H
System Manual, 03/2012, A5E00267695-11
13.4 Connecting redundant I/O to the PROFIBUS DP interface
Using I/Os in S7–400H
185