Daikin VRV REYQ96MTJU Design, Installation & Testing Instruction page 85

Hide thumbs Also See for VRV REYQ96MTJU:
Table of Contents

Advertisement

Si39-406
The following settings are made by pushbutton switches on PC board.
In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED indication as shown below.
Master unit
Slave unit 1
Slave unit 2
There are the following three setting modes.
Initial status (when normal) : Indicates during "abnormal", "low noise control" and "demand control".
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
Used to check the program made in Setting mode 2.
General Information
Setting by pushbutton switches
H1P
H2P
7
7
7
7
7
7
Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
Mode changing procedure
Press BS1 (MODE button) for more than 5 sec.
Setting mode 2
Setting item selection (Set)
Press BS3
(RETURN button).
Setting condition
selection (Set)
Press BS3
(RETURN button).
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS1
(MODE button).
H3P
H4P
H5P
8
7
7
7
7
7
7
7
7
BS1
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
RESET
(V2760)
(Normal)
Push the BS1(MODE button)
one time.
Setting mode 1
MODE
Off
H1P
(Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1(MODE button).
(Initial condition)
Test Operation
H6P
H7P
H8P
7
7
8
7
7
9
7
7
7
(Factory setting)
Monitor mode
MODE
Blinking
H1P
(V2761)
Monitor mode
Check item selection (Set)
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Press BS1
(MODE button).
(V2762)
79