Daikin VRV REYQ96MTJU Design, Installation & Testing Instruction page 109

Hide thumbs Also See for VRV REYQ96MTJU:
Table of Contents

Advertisement

Si39-406
7.2.3 Branch with refnet header
(Connection of 8 indoor units Heat pump system)
Between outdoor
Maximum
and indoor units
allowable
length
• Actual pipe length
Pipe length between outdoor and indoor units ≤ 330ft.
Example unit 6: a + o ≤ 330ft.
• Equivalent length
Equivalent pipe length between outdoor and indoor units ≤ 390ft.
(assume equivalent pipe length of refnet joint to be 1.6ft., that of refnet header to be 3.3ft.,
calculation purposes)
• Total extension length
Total piping length from outdoor unit* to all indoor units ≤ 950ft.
Allowable
Between outdoor and indoor units
• Difference in height
height
Difference in height between outdoor and indoor units (H1) ≤ 164ft.
length
(Max 130ft. if the outdoor unit is below)
Between indoor and indoor units
• Difference in height
Difference in height between adjacent indoor units (H2) ≤ 49ft.
• Actual pipe length
Allowable
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit ≤ 130ft.
length after
Example unit 8: o ≤ 130ft.
the branch
General Information
One outdoor
unit installed
BS unit
Indoor unit
Cool/Heat selection possible
Branch with refnet header
Outdoor unit
a
b
d
f
B1
B2
B3
(
~
)
B1
B6
c
e
g
i
(
~
)
1
2
3
1
8
(
~
)
1
6
REFNET header
h
j
l
n
o
B4
B5
B6
k
m
4
5
6
7
H2
8
.
Cooling only
(
)
7
8
Appendix
H1
103