Selection of Location
2. In heavy snowfall areas, select an installation site where snow will not affect operation of the
WARNING
1. The refrigerant R410A itself is nontoxic, nonflammable and safe. If the refrigerant should leak
2. Do not install in the following locations.
142
unit.
however, its concentration may exceed the allowable limit depending on room size. Due to this
it could be necessary to take measures against leakage.
Refer to the chapter "Caution for refrigerant leaks".
Locations such as kitchens which contain a lot of mineral oil or steam in the atmosphere or
where oil may splatter on the unit.
Resin parts may deteriorate, causing the unit to fall or leak.
Locations where sulfurous acids and other corrosive gases may be present in the
atmosphere.
Copper piping and soldered joints may corrode, causing refrigerant to leak.
Locations where equipment that produces electromagnetic waves is found.
The electromagnetic waves may cause the control system to malfunction, preventing normal
operation.
Locations where flammable gases may leak, where thinner, gasoline, and other volatile
substances are handled, or where carbon dust and other incendiary substances are found in
the atmosphere.
Leaked gas may accumulate around the unit, causing an explosion.
Si39-406
Installation Manual REYQ96MTJU