Installation
1. Execute the installation work by checking the foundation strength and levelness to avoid any occurrence of
Caution
Install the unit securely in case of earthquake an typhoon, cyclone, hurricane or other strong wind. The unit
may topple or cause another accident if improperly set up.
Unpacking and
Placing the Unit
Q96 type
DO NOT USE STANDS TO SUPPORT THE CORNERS
Note:
1. Prepare a water drainage channel around the foundation to condensate waste water from
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of 5 14/
60
Caution in installation
vibration and noise.
Fix the unit tightly with foundation bolts. (Prepare 4 sets of M12 foundation bolts with proper nuts and
washers.)
The proper length of the foundation bolts form the surface of the base is 13/16".
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
Secure the unit to its base using foundation bolts. (Use four commercially available M12-type
foundation bolts, nuts, and washers.)
The foundation bolts should be inserted 13/16".
Make sure the base under the unit extended more than 30 1/8" behind the unit.
The height of the base should be at least 5 7/8" from the floor.
The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as
indicated in the figure below.
Model
A (in.)
48 13/16
1
around the unit.
first.
16" under the unit in order to prevent infiltration of water coming from under the unit.
1. Foundation bolt point (φ9/16"
A
1
dia. : 4 positions)
B
2. Depth of product
3. Shape of indoor unit's support
leg and foundation bolt
positions
2
3
(in.)
B (in.)
43 3/8
1. Do not use stands to
support the corners.