Test Operation
Air Flow
Make the following setting according to the ceiling height. The setting position No. is set to "01" at
the factory.
Adjustment -
Ceiling Height
Mode
13 (23)
Mode
13 (23)
Air Flow Direction
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting
Setting Table
72
In the Case of FXAQ
Setting Switch
Mode No.
No.
13(23)
0
In the Case of FXFQ12~30
First
Second
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
In the Case of FXFQ36
First
Second
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
Mode No.
First Code No.
13 (23)
1
Setting Position
No.
01
Wall-mounted type : Standard
02
Wall-mounted type : Slight increase
03
Wall-mounted type : Normal increase
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
Setting
4-way Outlets
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Si39-406
Setting
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Setting
General Information