Specifications - YASKAWA SI-N3 Installation Manual

Ac drive-option card devicenet
Hide thumbs Also See for SI-N3:
Table of Contents

Advertisement

9

Specifications

Specifications
Items
Model
SI-N3
Group 2 Server (UCMM capable)
Explicit Messages: Fragmentation is supported. Up to 32 bytes can be input and output.
Polled I/O Messages: Fragmentation is not supported. Up to 8 bytes can be input and output.
SI-N3 Supported
Faulted Node Recovery / Offline Connection Set Messages / Automatic Device Replacement
Messages
(ADR)
Change of State Message (COS).
COS can be used as an I/O Input Assembly.
I/O Assembly
Input: 17 types (4~8 bytes)
Instance
Output: 18 types (4~8 bytes)
DeviceNet
Conformance Level 19: Passed
Specification
DeviceNet Profile AC Drive
Voltage: 11~25 Vdc
Input Power
Current: 40 mA
Connector Type
5-pin open-style screw connector
Physical Layer
Isolated Physical Layer
Type
CAN transceiver + photocoupler
Programmable from drive keypad or network:
MAC ID Setting
MAC ID 0 to 63
Programmable from drive keypad or network:
125/250/500 k bit/s
Communications
Auto Baud Rate
Speed/Baud Rate
Idle Mode Detect
Heartbeat
Ambient
–10 °C to +50 °C
Temperature
Humidity
up to 95% RH (no condensation)
Storage
–20 °C to +60 °C (allowed for short-term transport of the product)
Temperature
Area of Use
Indoor (free of corrosive gas, airborne particles, etc.)
Altitude
up to 1000 m
YASKAWA ELECTRIC TOBP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Installation Manual
Table 11 Option Specifications
Specifications
9 Specifications
31

Advertisement

Table of Contents
loading

Table of Contents