When installing any type of fryer, Standard No. 96 of the National Fire Protection Association must
be followed implicitly.
The duct system, the hood and filter bank must be cleaned on a regular basis and kept free of
grease according to the NFPA Standard No. 96.
A copy of the standard may be obtained from the National Fire Protection Association, Battery
March Park, Quincy, MA 02269 or at www.NFPA.org.
2.1.2 Electrical Grounding Requirements
All electrically operated appliances must be grounded in accordance with all applicable national
and local codes, and, where applicable, CE codes. In the absence of local codes, the appliance must
be grounded in accordance with National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.2, as applicable. All units (cord connected or permanently connected) should be
connected to a grounded power supply system. Wiring diagrams are supplied
with the fryer. Refer to the rating plate on the inside of the fryer door for proper
voltages.
The equipotential grounding lug indicated by illustration (right) allows all the
equipment in the same location to be electrically connected to ensure there is no
electrical potential difference between the units, which could be hazardous.
This appliance is equipped with a special (grounding) plug for your protection against
electrical shock and must be plugged directly into a properly grounded receptacle. Do not
cut, remove, or otherwise bypass the grounding prong on this plug!
2.1.3 Australian Requirements
To be installed in accordance with AS 5601 / AG 601, local authority, gas, electricity, and any other
relevant statutory regulations.
2.2

Power Requirements

The three-phase supply plug for the elements, controls and filter is rated at 60 amps, 250 VAC and
is NEMA configuration L15-60P. Each fryer should have its own individual cord for the element
supply on an individual circuit.
VOLTAGE
208
240
480
220/380
240/415
230/400
WIRE
MIN.
PHASE
SERVICE
3
3
3
3
3
3
3
4
3
4
3
4
DANGER
AWG
SIZE
(mm
)
L1
2
6
(16)
39
6
(16)
34
8
(10)
17
6
(16)
21
6
(16)
20
6
(16)
21
2-3
AMPS PER LEG
L2
L3
39
39
34
34
17
17
21
21
20
21
21
21