MAP5000
Automatic bypassing of points can be optionally programmed.
Automatic Arming at a Predefined Time Without Warning Signal
Define arming time
Automatic bypassing of points can be optionally programmed.
Automatic Arming after Disarming Without Warning Signal
Define arming time
Automatic bypassing of points can be optionally programmed.
Disarming at a Predefined Time
Automatic disarming is not permitted for security reasons.
8.3.3

Areas with Blocking Time

Disarming of an area can be optionally influenced by means of a blocking time. An external
alarm from the area cancels the blocking time, i.e. disarming is possible.
8.3.4

Access Levels

The SES standard distinguishes between four basic access levels (AE), whereby a further
access level 2A is a subset of access level 2B. This must be additionally present in accordance
with the section Functions of the Access Levels, page 66.
AE 1 Access for everyone, no authorization/code required
AE 2A Access for users, user passcode required
AE 2B Access for users, user passcode required
AE 3 Access for installers via control center
1.
2.
3.
AE 3 Access for installers via RPS for MAP
1.
2.
Bosch Sicherheitssysteme GmbH
Program the duration of the acoustic warning signal before arming in the area: Area
Manager > Area > Exit Delay > Normal Delay Time
The option Arm Only If Area Is Ready To Arm must be deactivated.
For requirements, refer to Arming with Automatic Bypass, page 76
Start the schedule wizard and define the time of arming.
As action, select Arm Area(s) Immediately.
For requirements, refer to Section Arming with Automatic Bypass, page 76
Enter the duration after disarming when automatic arming is to take place in the area.
Area Manager > Area > Behavior > Automatic Arming after Disarming
For requirements, refer to Arming with Automatic Bypass, page 76
Under Area (Area Manager), select the desired Time Model. Please note: Disarming is
possible within a defined time interval.
A Time Model is made up of Day Models and can be adapted or created in the User
Manager if necessary.
A blocking time can be changed by the user at the control center up to seven days in
advance if the user has the corresponding permissions. User Manager > Permission Sets
> Operations Category > May Edit Blocking Time
Open control panel enclosure => Internal warning device is activated for 3 sec. 1
Switch on Installer Mode (refer to Installer Button, page 67)
Enter installer passcode
Open control panel enclosure => Internal warning device is activated for 3 sec. 1
or
authorization from RPS by a AE 2 user with corresponding
permissions (control center: Main menu page 2 > RPS)
Establish connection of panel to RPS
Installation Manual
Appendices | en
81