44
en | Cable Connections
Figure 3.7 Mount the Thermistor
3.5

Make the LSN Gateway Connections

Notice!
When connecting an LSN component, ensure that you follow local standards and guidelines
when planning the system installation.
The following applies for VdS systems: Each area must be supplied with power
independently. The outputs AUX1 and AUX2 on the LSN gateway (for max. two areas) or the
voltage outputs of the fuse plate (SIV) (for additional areas) are available for this purpose.
For both stub and loop wiring, the following additional requirements apply for shielded wires:
Other connections of the additional shielding wire at other locations are not permitted. With
loop wiring, the additional shielding wire must be connected at both loop ends.
2014.12 | 13 | F.01U.168.332
always with additional shielding wire from the central unit
routed across the shortest possible distance to the earth terminal
looped through the LSN elements
Installation Manual
MAP5000
Bosch Sicherheitssysteme GmbH