Table 4: Maximum D8128D Connections; Table 5: Number Of D8128Ds Used With D8129S - Bosch D8128D Installation Manual

Octopopit module
Hide thumbs Also See for D8128D:
Table of Contents

Advertisement

Note:
As shown in Table 3, D8128A OctoPOPITs cannot be used on the new D7212, D7212G, D7412, D7412G, D9112,
D9412, or D9412G Control Panels. However, D8128D OctoPOPITs may be used and intermixed with D8128A
OctoPOPITs on the D7212B1 and D9112B1 Control Panels.
The maximum number of D8128D Modules that can be connected to your system depends on the control panel being
used (see Table 4). Please refer to Table 7 through Table 10 for proper switch settings.
The number of D8129 OctoRelays that can be connected to each Zonex terminal on the D9412G panels is limited by the
number of D8128D OctoPOPITs connected.
Using D8129 OctoRelays and D8128D OctoPOPITs together on the same Zonex Terminals is limited and
depends on the number of D8128D OctoPOPITs and D8129 OctoRelays connected to a single Zonex Bus.
Refer to Table 5 for information on the maximum number of D8128Ds and D8129s that may be connected
to a single Zonex Bus.
© 2004 Bosch Security Systems, Inc.
Control Panel
D9412G
D9412
D9112
D9112B1
D9124 w/D9112LTB
D9124 w/D9112LTB-EX
D9124 w/D9412GLTB
D7412G
D7412
D7212
D7212B1
D7212G
*Three points may be used on the last octopopit.

Table 4: Maximum D8128D Connections

Number of D8128Ds
Connected to a Single
ZONEX Bus
9
10
11
12
13
14

Table 5: Number of D8128Ds used with D8129s

D8128D Installation Guide
Page 5
Max. # of D8128D's
30
30
30
16
16
30
30
9*
9*
9*
5
4
Maximum Number
of D8129s that can
be Connected
6
5
4
3
1
1
D8128D
D8128D Overview
41343F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents