8.5

Malfunctions when establishing an outgoing call

8.5.1

Check connection establishment

Procedure for checking the connection establishment
1. In the "Parameters > Outgoing Calls" tab, set the "Connection establishment" parameter
2. In the "Parameters > Outgoing Calls" tab, set the "Connection establishment" parameter
In the "Information > Status" tab of the configuration interface, you can view the status of the
connection establishment for the outgoing Call.
8.5.2

The modem connection is not made

Diagnostics
The modem connection is not made. The DCD LED on the TS Adapter IE or on the external
modem remains unlit.
Remedy
1. Check the phone cables and the power connection of the TS Adapter IE.
2. Check the phone number in the "Parameters > Outgoing Calls" tab.
3. Check the following parameter in the "Parameters > Modem > Internal Modem" or
TS Adapter IE
Manual, 11/2010, A5E00977705-03
to "never" and click "Save Setting".
Any active connection establishment is aborted.
to "always" and click "Save Setting".
A new connection establishment is initiated.
"Parameters > Modem > External Modem" tab:
– To access an outside line, first dial
– Dial procedure
– Wait for dial tone
Activate this check box only if you are operating the modem on a main line.
8.5 Malfunctions when establishing an outgoing call
Error diagnostics
73