Siemens SINUMERIK 840D sl Commissioning Manual page 952

Basesoftware and operating software
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Configuring the system
2.4 PCU with SITOP UPS module
General settings
The following settings must be made in the SITOP monitor configuration dialogue box:
● Parameterization of the interface: For module with USB port
● Parameterization of the change action:
Parameterization of the SITOP monitor
Enter the path of the program that ensures that HMI Advanced and the PCU shut down
properly in the event of a power failure into the parameter area of the buffer.
E:\SITOP\Shutdown.bat
Figure 2-4
Alternatively, the following setting can be used: E:\Windows\system32\hmiexit.exe
58
The monitoring window display must be deselected, as this function can lead to sporadic
faults on the HMI operator interface.
Figure 2-3
Configuration of the SITOP monitor: General settings
Configuration of the SITOP monitor: Buffering settings
Commissioning Manual, 02/2012, 6FC5397-1DP40-3BA0
PCU-Basesoftware (IM8)