A.2 Drive Specifications
Item
Efficiency
Power Factor
Cooling Method
Control Method
Main Circuit
Frequency Control
Range
Frequency Control
Accuracy
Analog Input
Resolution
Accel/Decel Time
Torque Accuracy
Overload Tolerance
Momentary Power
Loss Compensation
Time
<2>
Main Control
Functions
Protective Functions
PLC Functions (Optional)
Standard Communication
Functions
Communications
(Optional)
<3>
Input Transformer
Temperature Protection
Control Panel
Main Circuit
Protection Design
Ambient
Temperature,
Relative Humidity
Storage Temperature –20°C to +60°C (for very short term when handling)
Atmosphere
Painting
Form
Applicable Standards
<4>
<1> Adjustments, e.g. to parameters, are required after auto-tuning.
<2> When the momentary power loss compensation function is used, an uninterruptible power supply unit for the control power supply is needed
(this is an option).
<3> To use the communications function, additional wiring and the installation of an option card must be done.
For Ethernet or CP-215 communication, an optional expansion PLC board is required.
<4> UL and cUL standards: A waiting approval.
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Table A.3 Drive Specifications
Approx. 97% (At rated motor speed, 100% load)
Min. 0.95 (At motor rated speed, 100% load)
Forced air-cooling by fan (with failure detection)
Open Loop Vector Control (OLV), Closed Loop Vector Control (CLV), V/f control (for multiple motor
operation), Closed Loop Vector Control for SM (optional)
Voltage-type PWM control with multiple outputs connected in series
(Power Cell: 3-level output)
0.01 to 120 Hz
±0.5%
0.03 Hz
0.1 to 6000 s
±0.5% (OLV), ±3% (CLV)
<1>
Continuous rated current 100%, overload tolerance 110% for 1 minute and 120% for 15 seconds
Max. 2 seconds
Torque control, Droop control, Speed/torque control switch, Momentary power loss compensation, Speed
search, Overtorque detection, Torque limit, 17-step speed (max.), Accel/decel time switch, S-curve accel/decel,
Auto-tuning (rotational, stationary), Dwell, Cooling fan on/ off, Slip compensation, Torque compensation,
Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop, PID
control (with sleep function), MEMOBUS communication (RS-485, max. 115.2 kbps), Fault retry
Overcurrent, Overvoltage, Undervoltage, Output ground fault, Output open-phase, Overload, Cooling-fan
error, Transformer overheat, Motor overheat, etc.
Expansion PLC board
RS-232: Digital operator
RS-485: MEMOBUS (Modbus)
USB: DriveWizard Plus MV
Any one of PROFIBUS-DP, DeviceNet, Ethernet, or CP-215 can be installed.
Class H dry type, –5%/N/+5% tap, secondary multi-phase winding
Power Cells: protected by thermistor for temperature
Transformer: protected by thermometer PT100Ω
Status display, Fault display, Parameter setting, Parameter reference
Power Cell construction
IP40 (simplified dustproof type)
–5°C to +40°C, 85%RH max. (no condensing)
General environmental conditions, free from dust and corrosive gases
Altitude: Max. 2000 m
5Y7/1 semi-gloss both for inner and outer faces
Made of enclosing steel sheets, vertical standalone type, front maintenance type