Common Drive Specifications

Horsepower (kW) Range
Max Output Frequency
Max Output Voltage
Overload Rating
PWM Carrier Frequency
Range
Motor Control Method
Speed Regulation/Accuracy
Speed Range
Frequency Setting Resolution
Frequency Reference
Accuracy
Frequency Control Range
Speed Response
Starting Torque at Low Speed V/f
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Table A.4 Common Specifications
Item
200 V Class
(Single-Phase)
200 V Class
(Three-Phase)
400 V Class
(Three-Phase)
Hz
V
%
200 V Class
400V Class
V/f
Open Loop Vector
Open Loop Vector for PM
(for use with PM motors)
V/f
Open Loop Vector
V/f
Open Loop Vector
Open Loop Vector Control for
PM motors
Digital Reference
Analog Reference
Output Frequency Resolution
Digital Reference
Analog Reference
~
Open Loop Vector
A.3 Common Drive Specifications
Specification
0.1 - 4.0 kW HP (HD)
0.1 - 4.0 kW HP (HD)
0.2 - 4.0 kW HP (HD)
400 Hz standard, 1000 Hz optional
All models
(proportional to input voltage)
(ND) 120%, 1 minute
(HD) 150%, 1 minute
(ND) 2 kHz Low Noise.
(HD) 1-15 kHz (model dependent)
Yes
Yes (current vector)
Yes
+/-1%
+/-0.2%
40:1
100:1
10:1
Digital Command: 0.1 Hz (under 100 Hz)
1 Hz (100 Hz and higher)
Analog Command: Max Frequency
1/1000 (10 bit)
0.001 Hz
Digital Command: ±0.01% of max. output
frequency (-10~+50º C)
Analog Command: ±0.5% of maximum
output frequency (25º C±10º C)
0.01 to 400.0 Hz
5 Hz at 20º C±10º C
150% at 3 Hz
A