4.6 Auto-Tuning

4.6

Auto-Tuning

◆ Auto-Tuning Type

Select the optimal Auto-Tuning based on the conditions such as your application, control mode of the drive, and
installation environment of the motor. When selecting the Auto-Tuning to run, refer to the flowcharts shown in
Flowcharts on page
90.
Note: The Auto-Tuning parameters valid for the control mode set for A1-02 are shown.
Auto-Tuning for Induction Motors
This feature sets the following parameters for induction motors automatically.
• Motor parameters E1-
• F1-
parameters for speed feedback detection (only when Closed Loop Vector Control is set)
Type
Rotational Auto-Tuning
Stationary Auto-Tuning
for Line-to-Line
Resistance
Set the data indicated in
The information required for setting can be found on the motor nameplate or in the motor test report. For details on the
procedure for Auto-Tuning, refer to
Multiple Motors on page 91
Input Data
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Motor Base Frequency
Number of Motor Pole
Motor Base Speed
PG Number of Pulses Per
Revolution
Motor No-Load Current
Motor Rated Slip
Motor Iron Loss
<1> Set this when Closed Loop Vector control is selected.
94
and E2-
(E3-
Table 4.6 Types of Auto-Tuning for Induction Motors
Parameter
Application Condition and Benefit
Setting
• The motor can turn around during the Auto-Tuning:
T1-01 = 0
This allows the most precise control of the motor.
• Running with constant output
• Tunes the drive after the cable between the drive and
motor has been replaced with a cable over 50 m long.
T1-01 = 2
Assumes Auto-Tuning has already been performed.
• Drive and motor capacities differ.
Table 4.7
before starting Auto-Tuning.
Subchart A-1: Simple Motor Setup Using V/f Control, or Serial Operation of
or
Subchart A-2: High Performance Operation Using OLV or CLV on page
Table 4.7 Input Data for Auto-Tuning for Induction Motors
Parameter
Units
T1-02
kW
T1-03
V
T1-04
A
T1-05
Hz
T1-06
T1-07
min
T1-08
T1-09
A
T1-10
Hz
T1-11
W
, E4-
for motor 2)
Auto-Tuning Type (T1-01)
Rotational Auto-Tuning (0)
Yes
Yes
Yes
Yes
Yes
Yes
-1
<1>
No
No
No
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Control Mode to Be
Applied
Open Loop Vector Control
Closed Loop Vector Control
V/f Control
Open Loop Vector Control
Closed Loop Vector Control
92.
Auto-Tuning for
Line-to-Line Resistance (2)
Yes
No
Yes
No
No
No
No
No
No
No
Start-Up