Verifying Parameter Settings and Backing Up Changes

Use the verify mode to check all changes to parameter settings. Refer to
page
87.
Confirm that the parameter setting is correctly configured, and save the setting. Changing the parameter access level and
setting a password are also possible to prevent the set parameters from being carelessly changed.

◆ User Parameter Default Value (o2-03)

The changed parameter can be saved in the drive by setting o2-03 (User Parameter Default Value) to "1" (Set defaults.
Saves parameter settings as default values for a User Initialization.). After the parameter setting is saved, the set value of
o2-03 returns to "0" (No change) automatically. The set value of A1-03 (Initialize Parameters) automatically displays
1110 (User initialize), and initialization by user parameter set values becomes enabled.
No.
Name
User Parameter Default
o2-03
Value
A1-03
Initialize Parameters

◆ Access Level of Parameter (A1-01)

It is possible to display only A1-
only). After that, parameter setting change becomes disabled.
Also, when A1-01 (Access level of parameter) is set to "1" (User parameter), only the parameters registered in the user
parameter of A2 are to be displayed, so only the parameters necessary for the machine and application can be displayed.
No.
Name
A1-01
Access Level of Parameter
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions

4.9 Verifying Parameter Settings and Backing Up Changes

Description
Saves/clears the default values used for A1-03 (Initialize
Parameters).
0: No change
1: Set defaults. Saves parameter settings as default values for a
User Initialization.
2: Clear all. Clears the default settings that have been saved
for a User Initialization
After the user parameter set values are saved, 1110 (User
initialize) can be selected from A1-03 (Initialize Parameters).
Selects a method to initialize the parameter.
0: No initializing
1110: User initialize
(User parameter set values must have been saved using o2-
03.)
2220: Initialization with 2-wire sequence
(set the parameters to default setting)
and U -
by setting A1-01 (Access level of parameter) to "0" (Monitoring
Description
Selects an access level of parameter (set/monitor).
0: Operation only
(Set and monitor A1-01 and A1-04. U -
also be monitored.)
1: User parameters
(Only the parameters A2-01 to A2-16 for each application and
the recently changed parameters A2-17 to A2-32 can be set up
and monitored.)
2: Advanced Access
(Can set and monitor all parameters)
Verifying Parameter Changes: Verify Menu on
Setting
Range
0 to 2
0 to 5550
Setting
Range
parameters can
0 to 2
Default
0
0
Default
2
4
103