3.6 Control Circuit Wiring
Terminal
Screw
Terminal
Type
Ground
input
ED
terminals
Terminals
L19 to L25
for the PG
<1> Use shielded twisted-pair wires to input an external speed (frequency) reference.
<2> The size of the round crimp terminals must meet the standards in the country where the drive is being used.

◆ Wiring the Control Circuit Terminal

Observe the following precautions when wiring control circuits.
• Use shielded twisted-pair wires for analog I/O (terminals L1 to L9) wirings to prevent malfunctions caused by noise.
• Tighten all terminal screws to the specified tightening torque.
• Use round crimp terminals to connect signal wires to the terminal block.
• Use a Phillips screw driver to tighten terminal screws.
WARNING! Electrical Shock Hazard. Do not touch circuit boards while the power is on. Failure to comply could result in death or
serious injury.
NOTICE: When wiring the control circuit, separate it from the main circuit wiring (terminals R, S, T, U, V and W) and other power lines.
Improper grounding could result in drive malfunction.
NOTICE: Insulate the shielded wires of the drive, e.g. with tape, to prevent their contact with other signal lines or devices. Failure to
comply could result in drive or equipment malfunction due to short circuit.
72
Tightening
Applicable Gauge
Torque
Size
N•m
M5
2 to 2.5
M3.5
0.8 to 1.0
Recommended
Gauge
mm
2
mm
(AWG)
(AWG)
8 to 14
<2>
8 (8)
(20 to 14)
0.5 to 2
<2>
1.25 (12)
(20 to 14)
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Wire Type
2
600-V insulated vinyl sheathed cable
(VV)
Shielded twisted-pair wire
<1>