Capacity Tables
Outdoor air
Combination
temp.
(Capacity)
EDB (°F)
CTXS07L +
68.0
FDXS09L
77.0
86.0
89.6
95.0
104.0
109.4
114.8
CTXS09H +
68.0
CTXS09H
77.0
86.0
89.6
95.0
104.0
109.4
114.8
CTXS09H +
68.0
FDXS09L
77.0
86.0
89.6
95.0
104.0
109.4
114.8
FDXS09L +
68.0
FDXS09L
77.0
86.0
89.6
95.0
104.0
109.4
114.8
Symbols:
EWB
: Entering wet bulb temp.
EDB
: Entering dry bulb temp.
TC
: Total capacity
PI
: Power input
66
57.2
60.8
TC
PI
TC
kBtu/h
kW
kBtu/h
15.72
1.06
16.44
1.08
15.00
1.13
15.71
1.15
14.28
1.20
14.99
1.22
13.99
1.23
14.70
1.25
13.56
1.27
14.27
1.29
12.83
1.36
13.55
1.38
12.40
1.41
13.12
1.43
11.97
1.46
12.68
1.48
19.27
1.36
20.15
1.39
18.39
1.44
19.26
1.47
17.50
1.53
18.38
1.56
17.15
1.57
18.02
1.60
16.62
1.63
17.49
1.65
15.73
1.73
16.61
1.76
15.20
1.80
16.08
1.83
14.67
1.87
15.55
1.89
17.75
1.40
18.56
1.43
16.93
1.48
17.74
1.51
16.12
1.58
16.93
1.60
15.79
1.61
16.60
1.64
15.31
1.68
16.11
1.70
14.49
1.78
15.30
1.81
14.00
1.85
14.81
1.88
13.51
1.92
14.32
1.95
16.33
1.44
17.07
1.47
15.58
1.53
16.32
1.55
14.83
1.62
15.57
1.65
14.53
1.66
15.27
1.69
14.08
1.72
14.82
1.75
13.33
1.83
14.07
1.86
12.88
1.90
13.62
1.93
12.43
1.98
13.17
2.01
(°F)
(°F)
(kBtu/h)
(kW)
Indoor air temp. EWB (°F)
64.4
PI
TC
PI
TC
kW
kBtu/h
kW
kBtu/h
17.15
1.11
17.67
16.43
1.17
16.94
15.71
1.24
16.22
15.42
1.27
15.93
14.98
1.32
15.50
14.26
1.40
14.78
13.83
1.45
14.35
13.40
1.50
13.91
21.02
1.41
21.65
20.14
1.50
20.77
19.25
1.59
19.88
18.90
1.62
19.53
18.37
1.68
19.00
17.48
1.79
18.12
16.95
1.85
17.58
16.42
1.92
17.05
19.36
1.46
19.94
18.55
1.54
19.13
17.73
1.63
18.31
17.41
1.67
17.99
16.92
1.73
17.50
16.10
1.84
16.69
15.61
1.91
16.20
15.13
1.98
15.71
17.81
1.50
18.35
17.06
1.58
17.60
16.31
1.68
16.85
16.01
1.72
16.55
15.56
1.78
16.10
14.81
1.89
15.35
14.36
1.96
14.90
13.92
2.03
14.45
Note:
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2.
shows nominal (rated) capacities and power input.
3. TC and PI must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for
calculation.)
4. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft
SUPER MULTI NX 2/3/4MXS-G/J Series Heat Pump
67.0
71.6
PI
TC
PI
kW
kBtu/h
kW
1.12
18.58
1.15
1.19
17.86
1.21
1.26
17.13
1.28
1.29
16.85
1.31
1.33
16.41
1.36
1.41
15.69
1.44
1.46
15.26
1.49
1.52
14.82
1.55
1.43
22.77
1.47
1.52
21.89
1.55
1.60
21.00
1.64
1.64
20.65
1.68
1.70
20.12
1.74
1.81
19.23
1.84
1.87
18.70
1.91
1.94
18.17
1.98
1.48
20.97
1.51
1.56
20.16
1.60
1.65
19.35
1.69
1.69
19.02
1.73
1.75
18.53
1.79
1.86
17.72
1.90
1.93
17.23
1.96
2.00
16.74
2.03
1.52
19.30
1.55
1.60
18.55
1.64
1.70
17.80
1.74
1.74
17.50
1.78
1.80
17.05
1.84
1.91
16.30
1.95
1.98
15.85
2.02
2.06
15.40
2.09
EDUS121131
75.2
TC
PI
kBtu/h
kW
19.29
1.23
18.57
1.23
17.85
1.30
17.56
1.33
17.13
1.38
16.40
1.46
15.97
1.51
15.54
1.57
23.65
1.58
22.76
1.58
21.88
1.67
21.52
1.70
20.99
1.76
20.11
1.87
19.58
1.93
19.05
2.00
21.78
1.62
20.97
1.62
20.15
1.72
19.83
1.75
19.34
1.82
18.52
1.92
18.03
1.99
17.54
2.06
20.04
1.67
19.29
1.67
18.54
1.76
18.24
1.80
17.79
1.87
17.04
1.98
16.59
2.05
16.14
2.12
3D058842B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents