Hardware specifications
Specific requirements
Horizontal distance between mounting holes 465.1 mm (18.312 in)
Mounting bolts
Footprint
Anchoring
Capacity
Cable or conduit
Seismic

Power and grounding

As part of the installation planning, ensure that the site meets the power and grounding
requirements of Secure Router 4134.

Power supply specifications

The following table describes the chassis AC and DC power supply units.
Table 14: Power supply specifications
Power supply
250 W AC
660 W AC
50
Installation — Chassis
HEX WSHR HD (SLTD) TYPE TT
0.216-2412-24 class UNC-2B, 0.75 in long
(Avaya P/N p097f815, screw referenced in
the mounting flange kit)
600 mm x 600 mm (23.6 in x 23.6 in)
You must properly anchor the frame or rack
to the floor as cited in the frame- or rack-
specific instructions.
Any rack or frame must be able to support
the weight of a fully loaded shelf (or multiple
shelves) plus the associated cable weight.
In countries where codes require it, the frame
or rack must have cable conduit attachment
capabilities for power feeds.
The rack or frame must comply with the
zone-specific requirements of the installation
site. For example, for Zone 4, the PTE2000
frame with proper anchoring is required.
Input
90–269 V AC
+12 V DC at 250
Watts (20.83 Amp at
nominal voltage)
90–269 V AC
+12 V DC at 250
Watts (20.83 Amp at
nominal voltage)
Comments? infodev@avaya.com
19-inch rack
Output to router
components
N/A
+54 V DC at 410
Watts (8.2 Amp at
+54 V DC) (isolated
PoE output
August 2013