Enumerations may not match the TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat
Controllers with Dehumidification Capability Installation Instructions (Part No. 24-10787-6), TEC3000 Series
Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability Installation
Instructions
(Part No. 24-10788-0), TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation
Instructions (Part No. 24-10789-5), and TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked
Thermostat Controllers Technical Bulletin (LIT-12011956) for NAE releases prior to 7.x.
Table 6: Occupancy Determination
Sequence of Operation (Highest to Lowest Priority)
Manual
Occupancy
BI (BI1-S,
Occupancy
Mode
1
BI2-S)
(OCCOVRD
-MODE)
Occupied
–
Unoccupied
No Override
1
Closed
1
Open
Not
Configured
1.
Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current
state of the BI when configured as Occupancy.
2.
True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when
the schedule is not Occupied.
3.
When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual
Occupancy Mode is not No Override, or an Occupancy BI is configured.
4.
Built-in occupancy sensing (PIR) or EI configured for Motion NO or Motion NC.
5.
Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and
the Schedule is writing Not Set as the schedule.
Selecting Schedule Source
Scheduling
The TEC3000 thermostat controller can operate as a stand-alone unit with an internal schedule or scheduled with
an external schedule. The OCC-CONFIG object sets the method used for scheduling.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Temporary
Occupancy
2,
Schedule
Occupancy
(External or
3
Schedule)
(OCC-
CONFIG,
NET-OCC)
–
–
2
NOT
True
1
Occupied
3
NOT
True
Occupied
False
Occupied
Unoccupied
Standby
Not Set
Status Indicated
Motion
Effective
4
Occupancy
Sensor
(EFF-OCC)
–
Occupied-
Override
Unoccupied-
Override
Occupied
Unoccupied
Temp
Occupancy
Temp
Occupancy
True
Occupied
False
Standby
Disabled
Occupied
–
Unoccupied
Standby
5
True
Occupied
False
Unoccupied
Disabled
Occupied
20
Occupancy
Source
(OCCSOURCE-S)
Occ Override
Occupancy BI
Temp Occ
Temp Occ BI
Occupancy Sensor
Occupancy
Schedule
Occupancy Sensor
Occupancy
Schedule