Siemens SINAMICS G150 Operating Instructions Manual page 554

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Functions, monitoring, and protective functions
9.3 Extended functions
Figure 9-15
Activation
The synchronized bypass with overlap (p1260 = 1) function can only be activated using a
control signal. It cannot be activated using a speed threshold.
Parameterization
Once the bypass with synchronizer with degree of overlapping (p1260 = 1) function has
been activated, the following parameters must be set:
Table 9- 7
Parameters
r1261.0
r1261.1
p1266 =
p1269[0] =
p1269[1] =
p3800 = 1
p3802 = r1261.2
554
Typical circuit diagram for bypass with synchronizer with degree of overlapping
Parameter settings for bypass function with synchronizer with degree of overlapping
Signal "Command switch motor - power unit"
Signal "Command switch motor - line supply"
Control signal setting
Signal source for contactor K1 feedback
Signal source for contactor K2 feedback
Synchronization is activated
Synchronizer activation is triggered by the bypass function.
Description
Operating Instructions, 07/2016, A5E03347396A