6.8.2

Control via PROFIBUS

Diagnostics LED "COM (PROFIdrive)"
The PROFIBUS diagnostics LED is located on the front of the Control Unit. Its states are
described in the following table.
Table 6- 28
Description of the "COM" LED
Color
State
-----
OFF
Green
Continuous light
Green
0.5 Hz flashing
light
Red
0.5 Hz flashing
light
Red
2 Hz flashing light
Setting the PROFIBUS address
There are two ways to set the PROFIBUS address:
1. Via p0918
– To set the bus address for a PROFIBUS node using STARTER, first set the rotary
– Then use parameter p0918 to set the address to a value between 1 and 126.
2. Via the PROFIBUS address switches on the Control Unit
– The address is set manually to values between 1 and 126 using the rotary coding
Note
The rotary coding switches used to set the PROFIBUS address are located beneath the
cover.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when the Control Unit is ready for opera-
tion (see LED RDY).
Cyclic communication is taking place.
Cyclic communication has still not been fully established.
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller did not send a Global Control or it sent a defec-
tive Global Control (GC).
PROFIBUS master is sending incorrect parameter assignment/configuration
Cyclic bus communication has been interrupted or could not be established.
code switches to 0
(00
dec
switches. In this case, p0918 is only used to read the address.
6.8 Communication via PROFIBUS DP
Description
) and 127
(7F
).
hex
dec
hex
Operation
349