Siemens SINAMICS G150 Operating Instructions Manual page 387

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Table 6- 38
No.
1
2
3
4
5
6
7
Table 6- 39
Byte Bit
1
2
Assembly Object, Instance Number: 4 hex
Supported services
Class
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Instance Attribute
Service
Type
Name
get
UINT16
Vendor ID
get
UINT16
Device Type
- Siemens Drive
get
UINT16
Product code
get
UINT16
Revision
get
UINT16
Status
get
UINT32
Serial number
get
Short
Product name
String
Explanation for No. 5 of the previous table
Name
0
Owned
1
2
Configured
3
4 ... 7
Extended De-
vice Status
8 ... 11
12 ... 15
• Get Attribute single
Value/explanation
1251
0C hex
r0964[1]
See the following table
bits 0 ... 19: consecutive number;
bits 20 ... 23: Production identifier
bits 24 ... 27: Month of manufacture (0 = Jan, B =
Dec)
Bits 28 ... 31: Year of manufacture (0 = 2002)
Max. length 32 bytes
Description
0: Inverter is not assigned to any master
1: Inverter is assigned to a master
Reserved
0: EtherNet/IP basic settings
1: Modified EtherNet/IP settings
Reserved
0: Self-test or status not known
1: Firmware update active
2: At least one I/O connection with error
3: No I/O connections
4: Incorrect configuration in the ROM
5: Fatal fault
6: At least one I/O connection is active
7: All I/O connections in the quiescent state
8 ... 15: Reserved
Not used
Reserved
Instance
6.11 Communication via EtherNet/IP
• Get Attribute single
• Set Attribute single
Operation
387

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents