S5: Selector for voltage/current AI0, AI1
Table 4- 21
Note
Delivery condition
When delivered, both switches are set to current measurement (switch set to "I").
X522: 2 analog outputs, temperature sensor connection
Table 4- 22
Max. connectable cross-section: 1.5 mm²
AO xV: analog output voltage; AO xC: Analog output current
1)
Accuracy of the temperature measurement:
2)
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Selector for voltage/current S5
Switch
S5.0
Selector voltage (V) / current (I) Al0
S5.1
Selector voltage (V) / current (I) Al1
Terminal block X522
Terminal
Designation
1
AO 0V+
2
AO 0-
3
AO 0C+
4
AO 1V+
5
AO 1-
6
AO 1C+
7
+Temp
2)
8
-Temp
2)
Function
1)
You can set the following output signals using parame-
ters:
Voltage: -10 ... +10 V (max. 3 mA)
Current 1: 4 ... 20 mA (max. load resistance ≤ 500 Ω)
Current 2: -20 ... +20 mA (max. load resistance ≤ 500 Ω)
Current 3: 0 ... 20 mA (max. load resistance ≤ 500 Ω)
Resolution: 11 bits + sign
Continuously short-circuit proof
Temperature sensor KTY84-1C130/PT1000/PTC
Measuring current via temperature sensor connection:
2 mA
Electrical installation
4.9 Signal connections
Technical data