Viessmann Vitodens 200 Service Instructions Manual page 61

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Temperatures, boiler coding card and brief . . .
Constant temperature control unit
Press the following keys:
1. K + G simultaneously for
approx. 2 s.
The following values can be scanned, subject to the actual system equip-
ment level:
Brief scan
0
0
1
Software
version
Solar con-
trol unit
0: no solar
control
unit
E
0: no ex-
ternal de-
mand
1: external
demand
3
0
A
0
4
0
5
0
b
0
C
0
c
0
2. a/b
3. d
Display screen
System de-
Software version
signs 1 to 6
Control unit
Software version
Burner control unit
0: no exter-
External 0 - 10 V hook-up
nal block-
Display in %
ing
0: no external hook-up
1: external
blocking
0
Set boiler water temperature
0
Highest demand temperature
Burner control unit type
0
Set cylinder temperature
0
Max. output in %
Boiler coding card (hexadecimal)
Version
Equipment
Service scans
(cont.)
for the required scan.
Scanning is completed.
Software
version
Program-
ming unit
Software
0
version
External
extension
0: no exter-
nal exten-
sion
Equipment type
Version
Burner control unit
61