Coding
Code 2
(cont.)
Coding in the delivered condition
98:1
Viessmann system
number (in conjunction
with monitoring several
systems via
Vitocom 300)
9b:0
No minimum set boiler
water temperature with
external demand
9C:20
Monitoring LON users
When there is no re-
sponse from a user, va-
lues defaulted by the
control unit are used
after 20 min and a fault
message is issued
(only for weather-com-
pensated control units)
9F:8
Differential temperature
8 K; only in conjunction
with the mixer circuit
(only for weather-com-
pensated control units)
Boiler circuit, mixer circuit
A0:0
Without remote control
(only for weather-com-
pensated control units)
48
Possible change
98:1
System number adjusta-
to
ble from 1 to 5
98:5
9b:1
Minimum set boiler water
to
temperature adjustable
9b:127
from 1 to 127 °C (limited
by the boiler coding card)
9C:0
No monitoring
9C:5
Time adjustable from 5 to
to
60 min
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)