Code 2
(cont.)
Coding in the delivered condition
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
Without auxiliary func-
tion for DHW heating
(only for constant tem-
perature control units)
65:...
Information regarding
the type of diverter
valve (not adjustable)
67:40
With the Vitosolic:
Third set DHW tem-
perature = 40 °C
6F:100
Maximum output for
DHW heating 100 %,
defaulted by the boiler
coding card
71:0
DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
72:0
DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
Possible change
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary function: 1 x
daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
67:0
Without third set DHW
temperature
67:1
Third set DHW tempera-
to
ture adjustable from 1 to
67:60
60 °C (subject to the set-
ting of coding address
"56")
6F:0
Max. output during DHW
to
heating adjustable from 0
6F:100
to 100 %
71:1
"OFF" during DHW heat-
ing to the first set value
71:2
"ON" during DHW heat-
ing to the first set value
72:1
"OFF" during DHW heat-
ing to the second set
value
72:2
"ON" during DHW heat-
ing to the second set
value
Coding
45