Viessmann Vitodens 200 Service Instructions Manual page 56

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
F7:25
In "Standby mode", the
internal circulation
pump is permanently
ON (only for constant
temperature control
units)
F8:-5
Temperature limit for
terminating the reduced
mode -5 ºC, see exam-
ple on page 97.
Observe the setting of
coding address "A3".
(only for weather-com-
pensated control units)
F9:-14
Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 97.
(only for weather-com-
pensated control units)
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature by
20 %. See example on
page 98 (only for weath-
er-compensated control
units).
56
Possible change
F7:0
In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
In "Standby mode", the
to
internal circulation pump
F7:24
in operating mode will be
started 1 to 24 times per
day for 10 min respec-
tively.
F8:+10
Temperature limit adjus-
to
table from
F8:-60
+10 to -60 °C
F8:-61
Function disabled
F9:+10
Temperature limit adjus-
to
table from
F9:-60
+10 to -60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50%
FA:50