Viessmann Vitodens 200 Service Instructions Manual page 29

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Further details regarding the individual steps
Changing the slope and level
A Changing the slope
B Changing the level (vertical paral-
lel offset of the heating curve)
Commissioning, inspection, maintenance
(cont.)
1. Slope:
Change with coding address "d3"
in code 1.
Setting range 2 to 35 (equals slope
0.2 to 3.5).
2. Level:
Change with coding address "d4"
in code 1.
Setting range -13 to +40 K.
29